Go top
Conference paper information

Small-signal stability of type 4 wind generators as affected by the bandwidth of current and PLL controllers

R. Ávila-Martínez, J. García-Aguilar, L. Rouco, J. Renedo, L. Sigrist, A. García-Cerrada

27th International Symposium on Power Electronics, Electrical Drives, Automation and Motion - SPEEDAM 2024, Ischia (Italy). 19-21 junio 2024


Summary:

This paper investigates the small-signal stability of type 4 wind generators as affected by the bandwidth of current and phase-locked loop (PLL) controllers. Using eigenvalue and participation factor analysis, this paper shows that high frequency dynamics may become unstable if the bandwidth of the current controllers of the power electronic converters is high. It has also been found that the bandwidth of the PLL control should be a small fraction of the bandwidth of the current controllers.


Keywords: Type 4 wind generators, small signal stability, controller bandwidth.


Publication date: June 2024.



Citation:
Ávila-Martínez, R., García-Aguilar, J., Rouco, L., Renedo, J., Sigrist, L., García-Cerrada, A., Small-signal stability of type 4 wind generators as affected by the bandwidth of current and PLL controllers, 27th International Symposium on Power Electronics, Electrical Drives, Automation and Motion - SPEEDAM 2024, Ischia (Italy). 19-21 June 2024.

IIT-24-123C

Request Request the document to be emailed to you.